Product Details
Lugar de origen: Henan, China
Nombre de la marca: Zhenglan Cable
Certificación: 3C; ISO 9001:2015, ISO 14001:2005, OHSAS 18001:2007
Número de modelo: Área nominal: 144mm2 conductor desnudo de arriba Wire
Payment & Shipping Terms
Cantidad de orden mínima: 300 metros
Detalles de empaquetado: Tambor de madera, madera y tambor de acero, como petición del cliente
Tiempo de entrega: 15 días
Condiciones de pago: L/C, T/T,
Material: |
de aluminio y de acero |
Base: |
Normal o modificado para requisitos particulares |
Longitud del tambor de cable: |
400~1000meter por el tambor |
characted: |
Conductor desnudo |
Área nominal: |
18.4~1439 |
Tambor: |
De madera o hierro |
Material: |
de aluminio y de acero |
Base: |
Normal o modificado para requisitos particulares |
Longitud del tambor de cable: |
400~1000meter por el tambor |
characted: |
Conductor desnudo |
Área nominal: |
18.4~1439 |
Tambor: |
De madera o hierro |
APPLICATION: ACSR is mainly used as bare overhead transmission cable and as primary and secondary distribution cable. It is also suitable for laying across basins, rivers and valleys where special geographical teatures exist.
STANDARD
Basic design to BS 3242 / BS EN 50182 / IEC 61089 / ASTM B 399/B 399M / DIN 48201 -6 standards.
CONSTRUCTION ACSR cable bvconsists of aluminum wires. The aluminum wires are concentrically stranded.
This section deals with heat-treatable magnesium silicon type aluminium alloys to the applicable International Standard, the electrical and mechanical properties of which all fall within the values suggested by relevant standard. Conductors to all other recognized specifications can also be supplied. The alloys referred to have higher strength but lower conductivity than pure aluminium. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR; Having lower breaking loads than the later, their use becomes particularly favourable when ice and wind loadings are low.
(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.
ELECTRICAL PROPERTIES
density@20ºC | 2.70 kg/dm |
Temperature Coefficient@20°C | 0.00360 (°C) |
resistivity@20°C | 0.0326 Ohms mm2/m |
linear Expansivity |
23 x10-6 (°C) |
SERVICE CONDITIONS
Ambient Temperature | -5°C - 50°C |
Wind Pressure | 80 – 130kg/m |
Seismic Acceleration | 0.12 - 0.05g |
Isokeraunic level | 10 – 18 |
relative Humidity | 5 – 100% |
CONSTRUCTION PARAMETERS
• IEC 60189
Code | Nominal Area | Stranding | Overall Diameter | Weight | Rated Strength | Electrical Resistance | Current Rating* |
mm2 | No.x mm | mm | Kg/Km | KN | Ω/Km | A | |
16 | 18.4 | 7/1.83 | 5.49 | 50.4 | 5.43 | 1.7896 | 86 |
25 | 28.8 | 7/2.29 | 6.87 | 78.7 | 8.49 | 1.1453 | 113 |
40 | 46 | 7/2.89 | 8.67 | 125.9 | 13.58 | 0.7158 | 151 |
63 | 72.5 | 7/3.63 | 10.89 | 198.3 | 21.39 | 0.4545 | 200 |
100 | 115 | 19/2.78 | 13.9 | 316.3 | 33.95 | 0.2877 | 266 |
125 | 144 | 19/3.10 | 15.5 | 395.4 | 42.44 | 0.2302 | 305 |
160 | 184 | 19/3.51 | 17.55 | 506.1 | 54.32 | 0.1798 | 355 |
200 | 230 | 19/3.93 | 19.65 | 632.7 | 67.91 | 0.1439 | 407 |
250 | 288 | 19/4.39 | 21.95 | 790.8 | 84.88 | 0.1151 | 466 |
315 | 363 | 37/3.53 | 24.71 | 998.9 | 106.95 | 0.0916 | 535 |
400 | 460 | 37/3.98 | 27.86 | 1268.4 | 135.81 | 0.0721 | 618 |
450 | 518 | 37/4.22 | 29.54 | 1426.9 | 152.79 | 0.0641 | 663 |
500 | 575 | 37/4.45 | 31.15 | 1585.5 | 169.76 | 0.0577 | 706 |
560 | 645 | 61/3.67 | 33.03 | 1778.4 | 190.14 | 0.0516 | 755 |
630 | 725 | 61/3.89 | 35.01 | 2000.7 | 213.9 | 0.0458 | 809 |
710 | 817 | 61/4.13 | 37.17 | 2254.8 | 241.07 | 0.0407 | 866 |
800 | 921 | 61/4.38 | 39.42 | 2540.6 | 271.62 | 0.0361 | 928 |
Why you choose us?